Skip to product information
1 of 2

C-Tec CFP702E-4 CFP Economy 2 Zone Conventional Fire Alarm Panel

C-Tec CFP702E-4 CFP Economy 2 Zone Conventional Fire Alarm Panel

Regular price £108.86
Regular price Sale price £108.86
Sold out
Shipping calculated at checkout.

Custom printed panels are non-returnable.

Please upload the image, photo, or logo you would like printed on the LED panel.

Recommended image size:• 600 × 600 pixels or higher resolutionAccepted file formats:• JPG• PNG• PDF

Availability143 in stock

Vendor: C-Tec
Category: Fire Alarm
Tags:

Shipping Policy

Once you receive your order confirmation email, your order will be processed within 2–3 business days (excluding weekends and public holidays).

Installation & Safety

Installation must be carried out by a qualified electrician.
Ensure power is switched off before installation.
Suitable for indoor use.

View full product details

The C-Tec CFP702E-4 CFP Economy 2 Zone Conventional Fire Alarm Panel is a cost-effective, fully certified fire detection solution ideal for small to medium-sized installations. LPCB certified to EN54-2 and EN54-4 standards, this panel offers a comprehensive array of user and installer-friendly features at a competitive price point. Housed in an attractive flush or surface-mountable plastic enclosure, it provides two detector zones and four conventional sounder circuits, making it suitable for shops, offices, and communal areas. The intuitive interface features colour-coded buttons and combined keypad/keyswitch entry for secure and straightforward operation. With four open-collector outputs and class change/alert inputs, it delivers flexibility while maintaining simplicity. Note that this economy version has limited engineering functions and is not compatible with expansion boards or repeaters, making it a straightforward, no-frills solution for basic fire alarm requirements.

Key Features of C-Tec CFP702E-4 2 Zone Fire Alarm Panel

  • LPCB Certified to EN54-2 & EN54-4: Third-party certified by the Loss Prevention Certification Board for assured quality and compliance .

  • Two Detector Zones: Supports up to 25 detectors per zone (or 32 combined detectors/call points) with a maximum cable length of 500m per circuit .

  • Four Conventional Sounder Circuits: Provides up to 800mA total output current (4 x 200mA) for alarm devices .

  • Intuitive User Interface: Colour-coded buttons and combined keypad/keyswitch entry for straightforward user and engineer access .

  • Integral 1.5A Power Supply: EN54-4/A2 compliant switch-mode PSU with support for up to 2 x 12V 3.2Ah VRLA batteries .

  • Four Open-Collector Outputs: Includes Fire, Fault, Reset, and Remote outputs (30mA max sink current) .

  • Auxiliary Inputs: 'Class change' and 'Alert' inputs for external system control .

  • Flush or Surface Mountable: Supplied in an attractive plastic enclosure with no bezel required for a clean finish .

  • Low Quiescent Current: Only 25mA consumption in standby mode .

  • UK Manufactured: Built by C-TEC in the UK .

  • Fully Compatible: Works seamlessly with C-TEC's ActiV range of conventional fire detectors .

Technical Specifications



Specification Details
Brand C-Tec
Model CFP702E-4
Product Type 2 Zone Conventional Fire Alarm Panel
Approvals LPCB certified to EN54-2 & EN54-4 
Mains Supply 230V 50/60Hz (350mA max) 
Internal PSU 19V-28.5V (27V nominal), 1.5A total output 
Quiescent Current 25mA 
Max Battery Size 2 x 12V 3.2Ah VRLA 
Detector Zones 2 (Max 500m per circuit) 
Devices per Zone 25 detectors (or 32 combined detectors/call points) 
Sounder Circuits 4 (Max 500m per circuit) 
Sounder Output Current 4 x 200mA (800mA total) 
EOL Resistor Value 6800Ω (detector zone) / 6800Ω (sounder circuit) 
Open Collector Outputs 4 (Fire, Fault, Reset, Remote) 
Auxiliary Inputs Class Change, Alert 
Expansion None (not compatible with repeaters or relay cards) 
Dimensions (HxWxD) 380mm x 235mm x 96mm 
Mounting Flush or Surface mount
Weight 1.75kg (without batteries) 
IP Rating IP30 
Operating Temp -5°C to +40°C 

Fire Alarm

Frequently Asked Questions (FAQs)

1. What is the main difference between this 'Economy' panel and the 'Standard' CFP panel?
The Economy panel (CFP702E-4) has limited engineering functions and cannot be expanded with CFP repeaters, relay cards, or EN54-13 interface cards, unlike the Standard version .

2. How many detectors can I connect to this 2-zone panel?
You can connect up to 25 detectors per zone, or a combined total of 32 detectors and manual call points per zone, allowing for a maximum of 64 devices across both zones .

3. What size batteries does this panel support?
The panel supports up to two 12V 3.2Ah VRLA batteries connected in series, which fit within the enclosure. The minimum recommended battery size is 1.2Ah .

4. Can I mount this panel flush into a wall?
Yes, the panel is supplied in an attractive enclosure suitable for both surface and flush mounting. For flush mounting, a hole of 367mm (W) x 220mm (H) x 75mm (D) is required .

5. Is this panel compatible with third-party detectors?
While it is fully compatible with C-TEC's ActiV range , for compliance and reliable operation, it is always recommended to use detectors specified by the manufacturer or consult the installation manual.